• Fluke 1736 Three-Phase Energy Logger with Current Probes Fluke 1738 Brand New in Stock
  • Fluke 1736 Three-Phase Energy Logger with Current Probes Fluke 1738 Brand New in Stock
  • Fluke 1736 Three-Phase Energy Logger with Current Probes Fluke 1738 Brand New in Stock
  • Fluke 1736 Three-Phase Energy Logger with Current Probes Fluke 1738 Brand New in Stock
  • Fluke 1736 Three-Phase Energy Logger with Current Probes Fluke 1738 Brand New in Stock
  • Fluke 1736 Three-Phase Energy Logger with Current Probes Fluke 1738 Brand New in Stock

Fluke 1736 Three-Phase Energy Logger with Current Probes Fluke 1738 Brand New in Stock

After-sales Service: Yes
Warranty: 1year
Customized: Non-Customized
Screen Size: 4.3-Inch
SD Card Memory Size: 32G
Sampling Frequency: 10.24 kHz at 50/60 Hz, Synchronized to Mains Frequ
Gold Member Since 2023

Suppliers with verified business licenses

Rating: 5.0/5
Guangdong, China
Importers and Exporters
The supplier has import and export rights
High Repeat Buyers Choice
More than 50% of buyers repeatedly choose the supplier
In-stock Capacity
The supplier has In-stock capacity
Fast Delivery
The supplier can deliver the goods within 15 days
to see all verified strength labels (7)
  • Overview
  • Product Parameters
  • Packaging & Shipping
Overview

Basic Info.

Model NO.
Fluke 1736
Input Signal Frequency
50/60 Hz (42.5 to 69 Hz)
Maximum Input Voltage
1000 Vrms, CF 1.7
Transport Package
UPS/DHL/FedEx
Specification
9.50 IN* 16.00 IN* 11.50 IN
Trademark
FLUKE
Origin
USA
HS Code
8471606000
Production Capacity
50, 000 Pieces/Year

Product Description

Product Parameters

 

Fluke 1736 Three-Phase Energy Logger with Current Probes Fluke 1738 Brand New in Stock

Fluke 1736/EUS Three-Phase Power Logger with Fluke Connect Compatibility and Flexible Current Probes

  • 3-Phase Energy Logger EU/US Version
  • Key measurements: Automatically capture and log voltage, current, power, harmonics and associated power quality values.
  • Fluke Connect® compatible*: View data locally on the instrument or via Fluke Connect mobile app and desktop software.
  • Convenient instrument powering: Power instrument directly from the measured circuit.
  • Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance and downstream.
  • Measure all three phases and neutral: With included 4 flexible current probes.
  • Comprehensive logging: More than 20 separate logging sessions can be stored on the instruments. In fact, all measured values are automatically logged so you never loose measurement trends. They can even be reviewed during logging sessions and before downloading for real-time analysis.
  • Capture dips, swells, and inrush currents: Includes event waveform snapshot and high resolution RMS profile, along with date, timestamp and severity to help pinpoint potential root causes of power quality issues.
  • Bright, color touch screen: Perform convenient in-the-field analysis and data checks with full graphical display.
  • Optimized user interface: Capture the right data every time with quick, guided, graphical setup and reduce uncertainty about your connections with the intelligent verification function.
  • Complete "in-the-field" setup through the front panel or Fluke Connect App: No need to return to the workshop for download nd setup or to take a computer to the electrical panel.
  • Energy Analyze Plus application software: Download and analyze every detail of energy consumption and power quality state of health with our automated reporting.
View Product Details

 

 

Description

Fluke 1736/EUS - Portable Power Logger EU/US Version

 
  • Convenient instrument powering: Power instrument directly from the measured circuit.
  • Highest safety rating in the industry: 600 V CAT IV/1000 V CAT III rated for use at the service entrance and downstream.
  • Measure all three phases and neutral: With included 4 flexible current probes.
  • Key measurements: Automatically capture and log voltage, current, power, harmonics and associated power quality values.

The Fluke 1736 Three-Phase Power Logger is designed to give users the information they need to make crucial power qualiy and energy decisions as efficently and quickly as possible. Fluke has paired the 1736 with its Fluke Connect® mobile app and desktop software to give users immediate access to critical information anywhere. Out of the box, the 1736 is capable of automatically capturing and storing more than 500 PQ paramters.

Access and share data remotely with your team via the Fluke Connect® app so you can maintain safer working distances and make critical decisions in real-time, reducing the need for protective equipment, site visits and check-ins. Quickly and easily chart and graph measurements with the included Fluke Energy Analyze Plus software package.

Easy to Use

 

The four current probes are connected separately; the instrument automatically detects and scales the probes. The thin current probes are designed to easily get through tight conductor spacing and are easily set to 150 or 1500 A for high accuracy in nearly any application. An innovative tangle-free flat voltage lead makes connection simple and reliable and the instrument's intelligent 'Verify Connection' feature automatically checks to make sure the instrument is connected correctly and can digitally correct common connection issues without having to disconnect measurement leads. The detachable power supply can be conveniently and safely powered directly from the measured circuit-no more searching for power outlets or having to run multiple extension cords to the logging location.

Analysis and Reporting

 

Capturing logged data is just one part of the task. Once you have the data, you need to create useful information and reports that can be easily shared and understood by your organization or customers. Fluke Energy Analyze Plus software makes that task as simple as possible. With powerful analysis tools and the ability to create customized reports in minutes you'll be able to communicate your findings and quickly solve problems so you can optimize system reliability and savings
 

Manufacturer Specs

Specifications
Accuracy
Parameter Range Max. resolution Intrinsic accuracy at reference conditions
(% of reading + % of full scale)
Voltage 1000 V 0.1 V ± (0.2% + 0.01%)
Current i17xx-flex 1500 12"
 
150 A
1500 A
0.1 A
1 A
± (1% + 0.02%)
± (1% + 0.02%)
i17xx-flex 3000 24
 
300 A
3000 A
1 A
10 A
± (1% + 0.03%)
± (1% + 0.03%)
i17xx-flex 6000 36"
 
600 A
6000 A
1 A
10 A
± (1.5 % + 0.03%)
± (1.5 % + 0.03%)
i40s-EL clamp 4 A
40 A
1 mA
10 m A
± (0.7% + 0.02 %)
± (0.7% + 0.02 %)
Frequency 42.5 Hz to 69 Hz 0.01 H z ± (0.1%)
Aux input ± 10 V dc 0.1 mV ± (0.2% + 0.02%)
Voltage min/max 1000 V 0.1 V ± (1% + 0.1%)
Current min/max defined by
accessory
defined by
accessory
± (5% + 0.2%)
THD on voltage 1000% 0.1% ± 0.5
THD on current 1000% 0.1% ± 0.5
Voltage harmonics 2nd ...50th 1000 V 0.1 V ≥ 10 V: ± 5% of reading
< 10 V: ± 0.5V
Current harmonics 2nd ...
50th
defined by
accessory
defined by
accessory
≥ 3% of current range: ± 5% of reading
< 3% of current range: ± 0.15% of range
Unbalance 100% 0.1% ± 0.2
 
Intrinsic uncertainty ± (% of reading + % of range)1
Parameter Influence
quantity
iFlex1500 -12
150A/1500A
iFlex3000-24
300A/3000A
iFlex6000-36
600/6000A
i40s-EL
4A/40A
Active Power PActive Energy Ea PF = 0.99 1.2% + 0.005% 1.2% + 0.0075% 1.7% + 0.0075% 1.2% + 0.005%
Apparent Power S Apparent Energy Eap 0 = PF = 1 1.2% + 0.005% 1.2% + 0.0075% 1.7% + 0.0075% 1.2% + 0.005%
Reactive Power Q Reactive Energy Er 0 = PF = 1 2.5 % of measured apparent power
Power Factor PF Displacement Power FactorDPF/cosφ - ± 0.025
Additional uncertainty in % of range1 V P-N > 250 V 0.015% 0.0225% 0.0225 % 0.015%
 
Electrical specifications
Power supply
Voltage range 100 V to 500 V using safety plug input when powering from the measurement circuit
100 V to 240 V using standard power cord (IEC 60320 C7)
Power consumption Maximum 50 VA (max. 15 VA when powered using IEC 60320 input)
Efficiency ≥ 68.2 % (in accordance with energy efficiency regulations)
Maximum no-load consumption < 0.3 W only when powered using IEC 60320 input
Mains power frequency 50/60 Hz ± 15 %
Battery Li-ion 3.7 V, 9.25 Wh, customer-replaceable
On-battery runtime Four hours in standard operating mode, up to 5.5 hours in power saving mode
Charging time < 6 hours
Data acquisition
Resolution 16-bit synchronous sampling
Sampling frequency 10.24 kHz at 50/60 Hz, synchronized to mains frequency
Input signal frequency 50/60 Hz (42.5 to 69 Hz)
Circuit types 1-?, 1-? IT, split phase, 3-? delta, 3-? wye, 3-? wye IT, 3-? wye balanced, 3-?
Aron/Blondel (2-element delta), 3-? delta open leg, currents only (load studies)
Data storage Internal flash memory (not user replaceable)
Memory size Typical 10 logging sessions of 8 weeks with 1-minute intervals and 500 events 1
Basic interval
Measured parameters Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental
power, DPF, energy
Averaging interval User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min
Averaging time min/max values Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to
IEC61000-4-30
Aux, Power: 200ms
Demand Interval (Energy Meter Mode)
Measured parameters Energy (Wh, varh, VAh), PF, maximum demand, cost of energy
Interval User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off
Power quality measurements
Measured parameter Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD
A, TDD
Averaging interval 10 min
Individual harmonics 2nd ...50th harmonic
Total harmonic distortion Calculated on 50 harmonics
Events Voltage: dips, swells, interruptions, current: inrush current
Triggered recordings Full cycle RMS updated every half cycle of voltage and current (Urms1/2 according
to IEC61000-4-30)
Waveform of voltage and current
 
Electrical specifications cont.
Standards Compliance
Harmonics IEC 61000-4-7: Class 1
IEEE 519 (short time harmonics)
Power quality IEC 61000-4-30 Class S, IEC62586-1 (PQI-S device)
Power IEEE 1459
Power quality compliance EN50160 (for measured parameters)
Interfaces
USB-A File transfer via USB flash drive, firmware updates, max. supply current: 120 mA
WiFi File transfer and remote control via direct connection or WiFi infrastructure
Bluetooth Read auxiliary measurement data from Fluke Connect ® 3000 series modules
(requires 1738, or 1736 upgrade option)
USB-mini Data download device to PC
Voltage inputs
Number of inputs 4 (3 phases and neutral)
Maximum input voltage 1000 Vrms, CF 1.7
Input impedance 10 MΩ
Bandwidth 42.5 Hz - 3.5 kHz
Scaling 1:1 and variable
Measurement category 1000 V CAT III/600 V CAT IV
Current inputs
Number of inputs 4, mode selected automatically for attached sensor
Input voltage Clamp input: 500 mVrms/50 mVrms; CF 2.8
Rogowski coil input 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4; all at nominal
probe range
Range 1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 12"
3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 24"
6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 36"
40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL
Bandwidth 42.5 Hz - 3.5 kHz
Scaling 1:1 and variable
Auxiliary inputs
Number of inputs 2
Input range 0 to ± 10 V dc, 1 reading/s
Scale factor Format: mx + b (gain and offset) user configurable
Displayed units User configurable (7 characters, for example, °C, psi, or m/s)
Wireless connection
Number of inputs 2
Supported modules Fluke Connect ® 3000 series
Acquisition 1 reading/s
 
Environmental specifications
Operating temperature -10 °C to +50 °C (14 °F to 122 °F)
Storage temperature -20 °C to +60 °C (-4 °F to 140 °F), with battery: -20 °C to +50 °C (-4 °F to 122 °F)
Operating humidity 10 °C to 30 °C (50 °F to 86 °F) max. 95 % RH
30 °C to 40 °C (86 °F to 104 °F) max. 75 % RH
40 °C to 50 °C (104 °F to 122 °F) max. 45 % RH
Operating altitude 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV)
Storage altitude 12,000 m
Enclosure IP50 in accordance with EN60529
Vibration MIL-T-28800E, Type 3, Class III, Style B
Safety IEC 61010-1
    IEC Mains Input:Overvoltage Category II, Pollution Degree 2
    Voltage Terminals:Overvoltage Category IV, Pollution Degree 2
IEC 61010-2-031:CAT IV 600 V / CAT III 1000 V
Electromagnetic compatibility (EMC) EN 61326-1: Industrial CISPR 11: Group 1, Class A
Korea (KCC):Class A Equipment (industrial broadcasting and
communication equipment)
USA (FCC):47 CFR 15 subpart B. This product is considered an exempt device per
clause 15.103
Temperature coefficient 0.1 x accuracy specification/°C
General specifications
Color LCD display 4.3-inch active matrix TFT, 480 pixels x 272 pixels, resistive touch panel
Warranty Instrument and power supply: Two-years (battery not included)
Accessories: one-year
Calibration cycle: two-years
Dimensions Instrument: 19.8 cm x 16.7 cm x 5.5 cm (7.8 in x 6.6 in x 2.2 in)
Power supply: 13.0 cm x 13.0 cm x 4.5 cm (5.1 in x 5.1 in x 1.8 in)
Instrument with power supply attached: 19.8 cm x 16.7 cm x 9 cm
(7.8 in x 6.6 in x 3.5 in)
Weight Instrument: 1.1 kg (2.5 lb)
Power supply: 400 g (0.9 lb)
Tamper protection Kensington lock slot
i17xx-flex 1500 12" Flexible Current Probe specifications
Measuring range 1 to 150 A ac/10 to 1500 A ac
Nondestructive current 100 kA (50/60 Hz)
Intrinsic error at reference condition* ± 0.7 % of reading
Accuracy 173x + iFlex ± (1 % of reading + 0.02 % of range)
Temperature coefficient over operating temperature range 0.05 % of reading/°C 0.09 % of reading/°F
Working voltage 1000 V CAT III, 600 V CAT IV
Probe cable length 305 mm (12 in)
Probe cable diameter 7.5 mm (0.3 in)
Minimum bending radius 38 mm (1.5 in)
Output cable length 2 m (6.6 ft)
Weight 115 g
Probe cable material TPR
Coupling material POM + ABS/PC
Output cable TPR/PVC
Operating temperature -20 °C to +70 °C (-4 °F to 158 °F) temperature of
conductor under test shall not exceed 80 °C (176 °F)
Temperature, non-operating -40 °C to +80 °C (-40 °F to 176 °F)
Relative humidity, operating 15 % to 85 % non-condensing
IP rating IEC 60529:IP50
Warranty One-year
 
Model features
  1736 Power Logger 1738 Power Logger
  FLUKE-1736/B FLUKE-1736/EUS   FLUKE-1738/B FLUKE-1738/EUS  
Model Power logger basic version Power logger (EU and US)   Power logger advanced version Power logger advance version (EU and US)  
Functions
PQ Health (EN50160 analysis) Opt. Opt.    
IEEE 519 reporting Opt. Opt.   Opt. Opt.  
Fluke Connect ® module support
(up to 2 modules**)
Opt. Opt.    
Recording
Trend  
 
Waveform Snapshots + RMS profile Opt. Opt.    
Communication
USB (mini B)    
WiFi download of instrument data    
WiFi download via WiFi access point (requires registration)** Opt. Opt.   Opt. Opt.  
Included Accessories
WiFi only adapter** -   - -  
WiFi and BLE adapter** Opt. Opt.   Opt.  
USB flash drive (4GB)    
USB Cable    
3PHVL-173 Flat Cable    
1x red, 1x black 0.1m cable
 
 
1x red, 1x black 1.5m lead    
Alligator clips 4 4   4 4  
C173x Soft Case    
Color Coding set    
173x-Hanger kit Opt. Opt.    
MP1-Magnet Probe Opt. Opt.   4 4  
i173X-flex1500 12" Opt. 4   Opt. 4  
Line cord EU, UK,
US, AU, BR
EU, US, UK   EU, UK,
US, AU, BR
EU, US, UK  
Compatible Optional Accessories
173X- AUX analog adapter    
i17XX-flex1500 12" Current Probe    
i17XX-flex3000 24" Current Probe    
i17XX-flex6000 36" Current Probe    
i40s-EL Current Clamp    
IEEE 519 reporting opt    
1736 to 1738 upgrade
(1736/UPGRADE)
  - -  

Tech Specs

Power Measurement/Power Loggers Template

Input(power loggers) Single Phase, Three Phase
Type(Power loggers) Digital, Portable Hand Held
Maximum Current AC 1500 A 
Maximum Voltage AC 1000 V 
True RMS Yes
Power Quality Yes
Current Input Channels 4
Voltage Input Channels 4
Measurement Frequency 50 Hz, 60 Hz
Display (Energy Management) Digital, Graphical
Transient Capture No
Displays Waveform Yes
Energy Yes
Phasor Diagrams No
Power Factor (Power Quality) Yes
Harmonics Yes 
Total Harmonic Distortion Yes
Current Clamps Included Yes 
Blue Tooth Compatable Yes 
CAT Rating IV 
CAT Voltage Rating (V) 600V

Test Equipment General Attributes

Warranty 2 YEARS
Interfaces I/O Bluetooth, Wifi, USB 
Storage Internal Memory 
IP Rating IP50
Product Weight 3 LBS
Product Height 9.75 IN
Product Length 15.50 IN
Product Width 11.50 IN
Data Logging Yes
Calibration Included None
Power Supply Voltage 120V/220V Universal
Country of Origin Romania
Shipping Height 9.75 IN
Shipping Length 15.50 IN
Shipping Width 11.50 IN
 

 

Packaging & Shipping
Fluke 1736 Three-Phase Energy Logger with Current Probes Fluke 1738 Brand New in Stock
Fluke 1736 Three-Phase Energy Logger with Current Probes Fluke 1738 Brand New in Stock
Fluke 1736 Three-Phase Energy Logger with Current Probes Fluke 1738 Brand New in Stock
Fluke 1736 Three-Phase Energy Logger with Current Probes Fluke 1738 Brand New in Stock
Fluke 1736 Three-Phase Energy Logger with Current Probes Fluke 1738 Brand New in Stock
Fluke 1736 Three-Phase Energy Logger with Current Probes Fluke 1738 Brand New in Stock

 

As an important international instrument sales platform, our company has the authorization qualifications of many international first-line brands. Relying on the advanced digital information management platform and international procurement platform, we provide more than 100,000 instruments, industrial MRO products, industrial products and spare parts to global customers. Our business scope: industrial testing, non-destructive testing, gas testing, electrical testing, laboratory testing, water quality testing, environmental testing, medical testing...       So far, we have become an important partner of many global top 500 companies and well-known local Chinese companies. Create an efficient supply chain system to provide customers with strong supply guarantee.

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Gold Member Since 2023

Suppliers with verified business licenses

Rating: 5.0/5
Trading Company
Number of Employees
4
Year of Establishment
2023-07-25