After-sales Service: | Yes |
---|---|
Warranty: | 1 Year Warranty |
Brand: | Fluke |
Customized: | Customized |
Certification: | CE, ISO, RoHS |
Display: | Digital |
Suppliers with verified business licenses
Current Measurement
|
|
Measuring Range
|
0 to 2000 A DC or 1400 AC RMS
|
Autorange Facility
|
40 A/400 A/2000 A
|
Resolution
|
10 mA in 40 A range
100 mA in 400 A range 1 in 2000 A range |
Accuracy
|
|
DC and DC RMS
|
I > 10 A: ±1.5% rdg ±5 digits
I < 10 A: ±0.2 A |
AVG
|
I > 10 A: ±3% rdg ±5 digits
I < 10 A: ±0.5 A |
Pk
|
I > 10 A: ±5% rdg ±5 digits
I < 10 A: ±0.5 A |
AHr
|
I > 10 A: ±2% rdg ±5 digits
I < 10 A: ±0.5 AHr |
CF (Crest Factor)
|
1.1 ≤ CF < 3: ±3% rdg ±5 digits
3 ≤ CF < 5: ±5% rdg ± 5 digits Resolution: 0.01 |
RPL (Ripple)
|
2% ≤ RPL < 100%: ±3% rdg ±5 digits
100% ≤ RPL < 600%: ±5% rdg ± 5 digits Resolution: 0.01% |
Voltage Measurement
|
|
Measuring Range
|
0 to 825 V DC or AC RMS
|
Autorange Facility
|
4 V/40 V/400 V/750 V
|
Resolution
|
1 mV in 4 V range
10 mV in 40 V range 100 mV in 400 V range 1 V in 750 V range |
DC and DC RMS
|
V > 1 V: ±1% rdg ±5 digits
V < 1 V: ± 0.02 V |
AVG
|
V > 1 V: ±3% rdg ±5 digits
V < 1 V: ± 0.03 V |
Pk
|
V > 1 V: ±5% rdg ±5 digits
V < 1 V: ± 0.03 V |
CF (Crest Factor)
|
V > 1 V: ±5% rdg ±5 digits
V < 1 V: ±5% rdg ± 5 digits Resolution: 0.01 |
RPL (Ripple)
|
2% ≤ RPL < 100%: ±3% rdg ± 5 digits
100% ≤ RPL < 600%: ±5% rdg ± 5 digits Resolution: 0.1% |
Harmonics
|
|
THD (Total Harmonic Distortion)
|
1% ≤ THD < 100%: ±3% rdg ± 5 digits
100% ≤ THD < 600%: ±5% rdg ± 5 digits Resolution: 0.1% |
DF (Distortion Factor)
|
1% ≤ DF < 100%: ±3% rdg ± 5 digits
Resolution: 0.1% H02 ≤ Vharm < H13: ±5% rdg ± 2 digits H13 ≤ Vharm ≤ H30: ± 10% rdg ± 2 digits |
Watts Measurement (Single - and Three-Phase)
|
|
Measuring Range
|
0 to 1650 kW DC or 1200 kW AC
|
Autoranging Facility
|
4, 40, 400, 1650 kW AC
|
Resolution
|
1 W in 4 kW
10 W in 40 kW 100 W in 400 kW 1 kW in 1200 kW |
Accuracy
|
2.5% rdg ± 5 digits
W1ø <2 kW ± 0.08 kW W3ø <4 kW ± 0.25 kW |
VA Measurement (Single - and Three-Phase)
|
|
Measuring Range
|
0 to 1650 kVA DC or 1200 kVA AC
|
Autorange Facility
|
4, 40, 400, 1650 kVA
|
Resolution
|
1 VA in 4 kVA
10 VA in 40 kVA 100 VA in 400 kVA 1 kVA in 1200 kVA |
Accuracy
|
VA >2 kVA: 2.5% rdg ± 5 digits
VA <2 kVA: ±0.08 kVA |
VAR Measurement (Single - and Three-Phase)
|
|
Measuring Range
|
0 to 1250 kVAR
|
Autorange Facility
|
4, 40, 400, 1200 kVAR
|
Resolution
|
1 VAR in 4 kVAR
10 VAR in 40 kVAR 100 VAR in 400 kVAR 1 kVAR in 1200 kVAR |
Accuracy
|
VA >4 kVAR: 2.5% rdg ± 5 digits
VA <4 kVAR: ±0.25 kVAR |
Power Factor Range
|
0.3 >PF <0.99
|
Power Factor (Single - and Three-Phase)
|
|
Measuring Range
|
0.3 capacitive and 1.0 to 0.3 inductive (72.5° capacitive and 0 to 72.5° inductive)
|
Resolution
|
0.001
|
Accuracy
|
±3°
|
Frequency Range
|
15 Hz to 1 kHz
|
Displacement Power Factor
|
|
Measuring Range
|
0.3 capacitive and 1.0 to 0.3 inductive (72.5° capacitive and 0 to 72.5° inductive)
|
Resolution
|
0.001
|
Accuracy
|
±3°
|
Frequency Range
|
15 to 22 Hz and 45 to 65 Hz
|
Kilowatt Hour (kWHr)
|
|
Measuring Range
|
40,000 kWHr
|
Autorange Facility
|
1, 40, 400, 4000, 40,000 kWHr
|
Resolution
|
1 WHr in 4 kWHr
10 WHr in 40 kWHr 100 WHr in 400 kWHr 1 kWHr in 4,000 kWHr 10 kWHr in 40,000 kWHr |
Accuracy
|
kWHr >2 kWHr: ±3% ± 5 digits
kWHr <2 kWHr: ±0.08 kWHr |
All Watts /VA /VAR /PF Measurements
|
Frequency range: DC and 15 Hz to 1 kHz
Current range: 10 to 1400 A RMS Voltage range: 1 to 825 V RMS Maximum input: 825 V RMS/1400 A RMS Maximum overload: 1000 V RMS/10,000 A |
Frequency Measurement
|
|
Measuring Range
|
15 Hz to 1 kHz
|
Resolution
|
0.1 Hz
|
Accuracy
|
15 to 22 Hz ± 0.5% rdg
40 to 70 Hz ± 0.5% rdg 15 to 1000 Hz ± 1% rdg |
Current Range
|
10 to 1400 A RMS
|
Voltage Range
|
1 to 825 V RMS
|
Current Measurement
|
|
Ranges
|
10/20/40/100/200/400/1000/2000 A
|
Resolution
|
1 A in 40 A
10 A in 400 A 50 A in 2000 A |
Accuracy
|
±3% rdg ± 1 pixel
|
Maximum Overload
|
10,000 A
|
Voltage Measurement
|
|
Ranges
|
4/10/20/40/100/200/400/1000 V
|
Resolution
|
100 mV in 4 V
1 V in 40 V 10 V in 400 V 31.25 V in 1000 V |
Accuracy
|
±2% rdg ± 1 pixel
|
Maximum Overload
|
1000 V RMS
|
Frequency Range
|
DC and 15 to 600 Hz
|
Time Base
|
2.5, 5, 10, 25, 50 ms/div
|
Refresh Rate
|
0.5 seconds
|
Maximum Sampling Rate
|
15.625 kHz
|
Inrush Current Function
|
|
Ranges
|
40, 400, and 2000 A
|
Resolution
|
10 mA in 40 A range
100 mA in 400 A range 1 A in 2000 A range |
Accuracy
|
I > 10 A: ±5% rdg ± 1 pixel
I < 10 A: ±0.5 A |
Maximum Overload
|
Maximum overload 10,000 A or RMS x frequency <400,000
|
Capture Time
|
1, 3, 10, 30, 100, and 300 s
|
Maximum Sampling Rate
|
15.625 kHz
|
Logging Memory
|
|
Logging Areas
|
Three areas that can be used individually or combined into one large area
|
Averaging Periods
|
1, 2, 5, 10, 30 s, 1, 5, 10, 15 min, and custom
|
General Specifications
|
|
Display
|
Color transmissive LCD 320 x 240 pixels (70 mm diagonal) with 2 level backlight
|
Power Supply
|
Battery type 1.5 V Alkaline AA MN 1500 or IEC LR6 x 6
|
Battery Life Typically
|
>10 hours (backlight on full)
>12 hours (backlight reduced) |
Battery Eliminator BE345
|
Input: 110/230 V, 50/60 Hz
Output: 15 V DC, 300 mA |
Reference Conditions
|
All accuracies stated at 73.4 ± 1.8°F (23 ± 1°C)
|
Operating Temperature
|
32 to 122°F (0 to 50°C)
|
Temperature Coefficient of Current
|
≤± 0.15% of rdg per °C
|
Temperature Coefficient of Voltage
|
≤± 0.15% of rdg per °C
|
Maximum Relative Humidity
|
80 % for temperatures up to 87°F (31°C) decreasing linearly to 50% relative humidity at 104°F (40°C)
|
Maximum Operating Altitude
|
6561.7' (2000 m)
|
Mechanical
|
|
Cleaning
|
The unit can be cleaned with an Isopropanol impregnated cloth. Do not use abrasives or other solvents.
|
Jaw Capacity
|
2.3" (58 mm) diameter
|
Jaw Opening
|
2.4" (60 mm)
|
Dimensions
|
12 x 3.75 x 2" (300 x 98 x 52 mm
|
Weight
|
1.8 lbs (820 g) batteries included
|
Electrical Safety
|
|
Maximum Safe Working Voltages
|
Current measurement: 600 V AC RMS or DC between uninsulated conductor and ground
Voltage measurement: 600 V AC RMS or DC between either input terminal and ground, or 825 V between energized phase voltages (delta power config.) |
EMC
|
|
Emission
|
IEC/EN 61326-1:1997 class B
|
Immunity
|
IEC/EN 61326-1:1997
|
As an important international instrument sales platform, our company has the authorization qualifications of many international first-line brands. Relying on the advanced digital information management platform and international procurement platform, we provide more than 100,000 instruments, industrial MRO products, industrial products and spare parts to global customers. Our business scope: industrial testing, non-destructive testing, gas testing, electrical testing, laboratory testing, water quality testing, environmental testing, medical testing...
Suppliers with verified business licenses