Ideal for preventative maintenance applications, this 10 kV insulation tester kit evaluates trends and eliminates doubts by
improving worker safety and saving valuable time while conducting tests. In addition, this kit comes with an insulation tester, heavy-duty alligator clip leads, an IP67 hard carrying case, and more.
Features
* Know if a line voltage is present before starting a test - A warning function alerts the user that the line voltage is present
and gives the voltage reading up to 600 V AC or DC for increased user safety
* Select test voltages up to 10 kV
* CAT III 1000 V, CAT IV 600 V safety rating
* Selectable test voltages in 50 V steps from 250 to 1000 V, and 100 V steps above 1000 V
* Long battery life gives the user over 750 tests between charges
* Guard system eliminates the effect of surface leakage current on high-resistance measurements
* Historical tracking and trending of assets identify degradation over time, allows real-time decisions to be made in the field with Fluke Connect Assets (sold separately)
* Large digital/analog LCD for easy viewing
* Capacitance and leakage current measurement
* Ramp function for breakdown testing
* Resistance measurements up to 2 TΩ
* Timer settings up to 99 minutes for timed tests
Electrical Specifications
|
The tester's accuracy is specified for one year after calibration at operating temperatures of 0 to 35°C
For operating temperatures outside the range (-20 to 0°C and 35 to 50°C), add ±0.25% per °C, except on the 20% bands add ±1% per °C |
Insulation Resistance Measurement
|
|
250 V
|
Range:
<250 kΩ 250 kΩ to 5 GΩ 5 to 50 GΩ >50 GΩ Accuracy (± reading): Unspecified 5% 20% Unspecified |
500 V
|
Range:
<500 kΩ 500 kΩ to 10 GΩ 10 to 100 GΩ >100 GΩ Accuracy (± reading): Unspecified 5% 20% Unspecified |
1000 V
|
Range:
<1 MΩ 1 MΩ to 20 GΩ 20 to 200 GΩ >200 GΩ Accuracy (± reading): Unspecified 5% 20% Unspecified |
2500 V
|
Range:
<2.5 MΩ 2.5 MΩ to 50 GΩ 50 to 500 GΩ >500 GΩ Accuracy (± reading): Unspecified 5% 20% Unspecified |
5000 V
|
Range:
<5 MΩ 5 MΩ to 100 GΩ 100 GΩ to 1 TΩ >1 TΩ Accuracy (± reading): Unspecified 5% 20% Unspecified |
10,000 V
|
Range:
<10 MΩ 10 MΩ to 200 GΩ 200 GΩ to 2 TΩ >2 TΩ Accuracy (± reading): Unspecified 5% 20% Unspecified |
Bar Graph Range
|
0 to 1 TΩ
|
Insulation Test Voltage Accuracy
|
-0%, +10% at 1 mA load current
|
Induced AC Mains Current Rejection
|
2 mA maximum
|
Capacitive Load
|
Charging rate: 5 seconds per µF
Discharge rate: 1.5 seconds per µF |
Leakage Current Measurement
|
Range: 1 nA to 2 mA
Accuracy: ±(5% + 2 nA) |
Capacitance Measurement
|
Range: 0.01 to 15 µF
Accuracy: ±(15% rdg + 0.03 µF) |
Timer
|
Range: 0 to 99 minutes
Resolution setting: 1 minute Resolution indication: 1 second |
Live Circuit Warning
|
Warning range: 30 to 660 V AC/DC, 50/60 Hz
Voltage accuracy: ±(15% + 2 V) |
General Specifications
|
|
Software
|
FlukeView Forms™ basic software requires a PC running Windows XP, Vista, 7, or 8
|
Display
|
2.9 x 4" (75 x 105 mm)
|
Power
|
12 V lead-acid rechargeable battery, Yuasa NP2.8-12
Charger input (AC): 85 to 250 V AC 50/60 Hz 20 VA |
Environmental
|
Operating temperature: -4 to 122°F (-20 to 50°C)
Storage temperature: -4 to 149°F (-20 to 65°C) Humidity: 80% to 31°C decreasing linearly to 50% at 50°C Altitude: 6561.68' (2000 m) Enclosure sealing: IP40 |
Input Overload Protection
|
1000 V AC
|
EMC
|
EN 61326
|
Safety Compliance
|
IEC 61010-1: Overvoltage category II, Pollution Degree 2
IEC 61010-2-030: Measurement 600 V CAT IV/1000 V CAT III IEC 61557-1, IEC 61557-2 |
Dimensions
|
10.6 x 10.9 x 6.3" (269 x 277 x 160 mm)
|
Weight
|
8.2 lbs (3.7 kg)
|
Suppliers with verified business licenses