After-sales Service: | Yes |
---|---|
Warranty: | 1 Year |
Display Type: | Analogue and Digital |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Fluke 1623-2 KIT Basic Earth Ground Tester Kit with 1623-2, Cable Reels, Ground Stakes, Clamps, Case
* Stakeless earth ground rod testing using 2 clamps
* IP56 rated for outdoor use
* 4-pole Soil Resistivity testing
* USB data storage and transfer
* Selective earth ground rod testing using 1 clamp
* Professional carrying case
* 3- and 4-pole Fall of Potential, earth resistance loop testing
Temperature Range
|
|
Operating Temperature
|
14 to 122°F (-10 to 50°C)
|
Storage Temperature
|
-22 to 140°F (-30 to 60°C)
|
Temperature Coefficient
|
±0.1% of reading/°C <18°C >28°C
|
Intrinsic Error
|
Refers to the reference temperature range and is guaranteed for one year
|
Operating Error
|
Refers to the operating temperature range and is guaranteed for one year
|
Climatic Class
|
C1 (IEC 654-1), 23 to 115°F (-5 to 45°C), 5 to 95% RH
|
Protective Type
|
IP56 for case, IP40 for battery door according to EN60529
|
Safety
|
Protection by double and/or reinforced insulation maximum 50 V to earth. IEC61010-1: 300V CAT II, Pollution degree two
|
EMC (Emission Immunity)
|
IEC61326-1: Portable
|
Quality System
|
Developed, designed, and manufactured according to DIN ISO 9001
|
External Voltage
|
V external, maximum = 24 V (dc, ac <400 Hz), measurement inhibited for higher values
|
V Ext Rejection
|
>120 dB (16²⁄3, 50, 60, 400 Hz)
|
Measuring Time
|
Typical six seconds
|
Maximum Overload
|
250 V rms (pertains to misuse)
|
Auxiliary Power
|
6 x 1.5 V Alkaline (type AA LR6)
|
Battery Life Span
|
Typical >3000 measurements
|
RA 3-Pole Ground Resistance Measurement (IEC 1557-5)
|
|
Switch Position
|
RA 3-pole
|
Resolution
|
0.001 to 10 Ω
|
Measuring Range
|
0.020 Ω to 19.99 kΩ
|
Accuracy
|
±(2% rdg + 3 d)
|
Operating Error
|
±(5% rdg + 3 d)
|
Measuring Principle: Current/Voltage Measurement
|
|
Measuring Voltage
|
Vm = 48 V ac
|
Short-Circuit Current
|
>50 mA
|
Measure Frequency
|
128 Hz
|
Probe Resistance (RS)
|
Maximum 100 kΩ
|
Auxiliary Earth Electrode Resistance (RH)
|
Maximum 100 kΩ
|
Additional Error from RH and RS
|
RH[kΩ]RS[kΩ]/RA[Ω]0.2%
|
RA 4-Pole Ground Resistance Measurement (IEC 1557-5)
|
|
Switch Position
|
RA 4-pole
|
Resolution
|
0.001 to 10 Ω
|
Measuring Range
|
0.020 Ω to 19.99 kΩ
|
Accuracy
|
±(2% rdg + 3 d)
|
Operating Error
|
±(5% rdg + 3 d)
|
Measuring Principle: Current/Voltage Measurement
|
|
Measuring Voltage
|
Vm = 48 V ac
|
Short-Circuit Current
|
>50 mA
|
Measure Frequency
|
128 Hz
|
Probe Resistance (RS + RES)
|
Maximum 100 kΩ
|
Auxiliary Earth Electrode Resistance (RH)
|
Maximum 100 kΩ
|
Additional Error from RH and RS
|
RH[kΩ]RS[kΩ]/RA[Ω]0.2%
|
Monitoring of RS and RH with error indicator.
Automatic range selection. |
|
RA 3-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp)
|
|
Switch Position
|
RA 3-pole with clamp
|
Resolution
|
0.001 to 10 Ω
|
Measuring Range
|
0.020 Ω to 19.99 kΩ
|
Accuracy
|
±(7% rdg + 3 d)
|
Operating Error
|
±(10% rdg + 5 d)
|
Measuring Principle: Current/Voltage Measurement (with External Current Clamp)
|
|
Measuring Voltage
|
Vm = 48 V ac
|
Short-Circuit Current
|
>50 mA
|
Measure Frequency
|
128 Hz
|
Probe Resistance (RS)
|
Maximum 100 kΩ
|
Auxiliary Earth Electrode Resistance (RH)
|
Maximum 100 kΩ
|
Monitoring of RS and RH with error indicator.
Automatic range selection. Measurement is not performed if the current through the current clamp is too low. |
|
RA 4-Pole Selective Ground Resistance Measurement with Current Clamp (RA with Clamp)
|
|
Switch Position
|
RA 4-pole with clamp
|
Resolution
|
0.001 to 10 Ω
|
Measuring Range
|
0.020 Ω to 19.99 kΩ
|
Accuracy
|
±(7% rdg + 3 d)
|
Operating Error
|
±(10% rdg + 5 d)
|
Measuring Principle: Current/Voltage Measurement (with External Current Clamp)
|
|
Measuring Voltage
|
Vm = 48 V ac
|
Short-Circuit Current
|
>50 mA
|
Measure Frequency
|
128 Hz
|
Probe Resistance (RS)
|
Maximum 100 kΩ
|
Auxiliary Earth Electrode Resistance (RH)
|
Maximum 100 kΩ
|
Monitoring of RS and RH with error indicator.
Automatic range selection. Measurement is not performed if the current through the current clamp is too low. |
|
Stakeless Ground Loop Measurement (2 Clamps)
|
|
Switch Position
|
RA 4-pole 2 clamps
|
Resolution
|
0.001 to 10 Ω
|
Measuring Range
|
0.020 Ω to 19.99 kΩ
|
Accuracy
|
±(7% rdg + 3 d)
|
Operating Error
|
±(10% rdg + 5 d)
|
Measuring Principle: Stakeless Measurement of Resistance in Closed Loops Using Two Current Transformers
|
|
Measuring Voltage
|
Vm = 48 V ac
|
Measure Frequency
|
128 Hz
|
Noise Current (IEXT)
|
Maximum IEXT = 10 A (ac) (RA <20 Ω)
|
General Specifications
|
|
Display
|
1999 Digit LCD: Display with special symbols, digit height 25 mm, fluorescent backlight
|
User Interface
|
Instant measurement through TURN and START one button concept. The only operating elements are rotary switch and START button
|
Robust, Water and Dust Resistant
|
Instrument is designed for tough environmental conditions (rubber protective cover, IP56)
|
Memory
|
Internal memory storage up to 1500 records accessible via USB port
|
Dimensions
|
9.75 x 5.25 x 7.35" (250 x 133 x 187 mm)
|
Weight
|
2.43 lbs (1.1 kg) including batteries
16.8 lbs (7.6 kg) included accessories and batteries in carrying case |