After-sales Service: | Yes |
---|---|
Warranty: | 1 Year Warranty |
Display Type: | Digital Only |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Electrical Specifications | The tester's accuracy is specified for one year after calibration at operating temperatures of 0 to 35°C For operating temperatures outside the range (-20 to 0°C and 35 to 50°C), add ±0.25% per °C, except on the 20% bands add ±1% per °C |
Insulation Resistance Measurement | |
250 V | Range: <250 kΩ 250 kΩ to 5 GΩ 5 to 50 GΩ >50 GΩ Accuracy (± reading): Unspecified 5% 20% Unspecified |
500 V | Range: <500 kΩ 500 kΩ to 10 GΩ 10 to 100 GΩ >100 GΩ Accuracy (± reading): Unspecified 5% 20% Unspecified |
1000 V | Range: <1 MΩ 1 MΩ to 20 GΩ 20 to 200 GΩ >200 GΩ Accuracy (± reading): Unspecified 5% 20% Unspecified |
2500 V | Range: <2.5 MΩ 2.5 MΩ to 50 GΩ 50 to 500 GΩ >500 GΩ Accuracy (± reading): Unspecified 5% 20% Unspecified |
5000 V | Range: <5 MΩ 5 MΩ to 100 GΩ 100 GΩ to 1 TΩ >1 TΩ Accuracy (± reading): Unspecified 5% 20% Unspecified |
Bar Graph Range | 0 to 1 TΩ |
Insulation Test Voltage Accuracy | -0%, +10% at 1 mA load current |
Induced AC Mains Current Rejection | 2 mA maximum |
Capacitive Load | Charging rate: 5 seconds per µF Discharge rate: 1.5 seconds per µF |
Leakage Current Measurement | Range: 1 nA to 2 mA Accuracy: ±(5% + 2 nA) |
Capacitance Measurement | Range: 0.01 to 15 µF Accuracy: ±(15% rdg + 0.03 µF) |
Timer | Range: 0 to 99 minutes Resolution setting: 1 minute Resolution indication: 1 second |
Live Circuit Warning | Warning range: 30 to 660 V AC/DC, 50/60 Hz Voltage accuracy: ±(15% + 2 V) |
General Specifications | |
Software | FlukeView Forms™ basic software requires a PC running Windows XP, Vista, 7, or 8 |
Display | 2.9 x 4" (75 x 105 mm) |
Power | 12 V lead-acid rechargeable battery, Yuasa NP2.8-12 Charger input (AC): 85 to 250 V AC 50/60 Hz 20 VA |
Environmental | Operating temperature: -4 to 122°F (-20 to 50°C) Storage temperature: -4 to 149°F (-20 to 65°C) Humidity: 80% to 31°C decreasing linearly to 50% at 50°C Altitude: 6561.68' (2000 m) Enclosure sealing: IP40 |
Input Overload Protection | 1000 V AC |
EMC | EN 61326 |
Safety Compliance | IEC 61010-1: Overvoltage category II, Pollution Degree 2 IEC 61010-2-030: Measurement 600 V CAT IV/1000 V CAT III IEC 61557-1, IEC 61557-2 |
Dimensions | 10.6 x 10.9 x 6.3" (269 x 277 x 160 mm) |
Weight | 8.2 lbs (3.7 kg) |